WATCHDOG SECTION 5
Page 5-1
INTRODUCTION
WATCHDOG SECTION 5
The CX-10 watchdog timer may be used to reset the
CPU should modbus communication or program
execution stop. Watchdog timers are used primarily in
Basic programs.
Initially, a timeout value is set in register 30. Then the
program periodically writes a 0 to register 31.
Register 31 operates by incrementing once/second.
When its value equals that in register 30, the CPU will
reset. When the CPU resets, all relays are turned off and
all volatile integers and floats are erased.
Register Detail
30 Watchdog timeout value.
0 = disable watchdog
1-255 = Timeout seconds.
31 Watchdog timer value. This register
increments every second until it
matches the value in Register 30 or
until a 0 is written to this register.